Installation of the PHLOX II Control Unit can be carried out at any
orientation of the device.
The control unit may be positioned at the engine or on the rack carry-
ing the engine. However, this should be a position where it is subject
to low vibration and low ambient temperatures.
Max allowed PHLOX II vibration profile:
10 ... 24Hz, +/- 2mm
24 ... 64Hz, 0.24 m/s
64 ... 2000Hz, 5g
Shock absorbing dampers can be used for installation on customers
own account. Dampers are not scope of delivery. They have to be or-
dered separately.
The permitted maximum cable lengths must also be observed.
To avoid the occurrence of faults, the device must not be exposed to
any powerful magnetic fields.