6 Maintenance and Troubleshooting
Copyright © Huawei Technologies Co., Ltd.
Attribute
Alarm ID
Alarm Severity
Alarm Type
22634
Set to Major by default.
Equipment alarm
Impact on the System
After this alarm is generated, the WebUI stops updating parameter values of undetected
equipment and fails to send configuration signals. Maintain the equipment immediately.
Possible Causes
The board is not securely inserted.
The board is removed.
The board is faulty.
Procedure
Step 1 Securely insert the board and tighten the screws.
Step 2 Replace the faulty board.
----End
Clearing
This alarm is cleared when the board is securely inserted into the subrack and the
communication between the board and the ECC500 resumes.
6.2.2.2 MUE05A_AIDI_1 DI Alarm