Huawei ECC500
142 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ECC500
User Manual
5 UI Description
Copyright © Huawei Technologies Co., Ltd.
Parameter
Setting
Board COM
NOTE
The setting example indicates that the EA800 UPS is connected to the
COM2 port of the RS485 card in slot 3 of the ECC500. If the EA800 UPS
is connected to another port, set the number of the connected port.
Equipment Address
No need to be set.
Timeout
The default timeout interval is 2s. Set the parameter to the required
value.
Step 4 Click Add Equipment.
----End
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
5.2.4.4 Adding a UL33 UPS
Prerequisites
A UL33 UPS is connected to the ECC500. The UL33 UPS and ECC500 have been
powered on.
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
After a UL33 UPS is connected to the ECC500, add the UL33 UPS on the ECC500 WebUI.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Home > Equipment Manage.
Step 3 Select UL33UPS from the Equipment Type drop-down list box and set device parameters,
as shown in Figure 5-19. Table 5-6 describes the setting methods.