EasyManuals Logo

Huawei FusionModule800 User Manual

Huawei FusionModule800
508 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #210 background imageLoading...
Page #210 background image
Figure 4-149 Connecting the water detector
Step 4 Plan the installation position for the fastener of the water detection cable. Ensure
that the water detection cable placed on the fastener is in good contact with the
oor.
Step 5 Tear o the protection paper from the rear of the fastener, and then securely
attach the fastener to the
oor.
If the fastener cannot be securely attached to the oor, perform Step 6.
If the fastener can be securely attached to the oor, perform Step 7.
Step 6 Drill holes in the oor with the same dimensions as the expansion bolts for the
fastener. Use the expansion bolts to secure the fastener to the oor, as shown in
Figure 4-150.
Figure 4-150 Installing fasteners
NO TICE
When laying out the water detection cable, ensure that the water detector is close
to the Converged Cabinet to facilitate further cable connections.
Step 7 Place the water detection cable onto the fastener, secure the fastener, and keep
the water detection cable in close contact with the
oor, as shown in Figure
4-151.
FusionModule800 Smart Small Data Center
User Manual 4 Installation Guide
Issue 01 (2021-02-05) Copyright © Huawei Technologies Co., Ltd. 198

Table of Contents

Other manuals for Huawei FusionModule800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule800 and is the answer not in the manual?

Huawei FusionModule800 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule800
CategoryStorage
LanguageEnglish

Related product manuals