Figure 4-149 Connecting the water detector
Step 4 Plan the installation position for the fastener of the water detection cable. Ensure
that the water detection cable placed on the fastener is in good contact with the
oor.
Step 5 Tear o the protection paper from the rear of the fastener, and then securely
attach the fastener to the
oor.
● If the fastener cannot be securely attached to the oor, perform Step 6.
● If the fastener can be securely attached to the oor, perform Step 7.
Step 6 Drill holes in the oor with the same dimensions as the expansion bolts for the
fastener. Use the expansion bolts to secure the fastener to the oor, as shown in
Figure 4-150.
Figure 4-150 Installing fasteners
When laying out the water detection cable, ensure that the water detector is close
to the Converged Cabinet to facilitate further cable connections.
Step 7 Place the water detection cable onto the fastener, secure the fastener, and keep
the water detection cable in close contact with the
oor, as shown in Figure
4-151.
FusionModule800 Smart Small Data Center
User Manual 4 Installation Guide
Issue 01 (2021-02-05) Copyright © Huawei Technologies Co., Ltd. 198