Figure 4-149 Connecting the water detector
Step 4 Plan the installation position for the fastener of the water detection cable. Ensure
that the water detection cable placed on the fastener is in good contact with the
oor.
Step 5 Tear o the protection paper from the rear of the fastener, and then securely
attach the fastener to the
oor.
If the fastener cannot be securely attached to the oor, perform Step 6.
If the fastener can be securely attached to the oor, perform Step 7.
Step 6 Drill holes in the oor with the same dimensions as the expansion bolts for the
fastener. Use the expansion bolts to secure the fastener to the oor, as shown in
Figure 4-150.
Figure 4-150 Installing fasteners
NO TICE
When laying out the water detection cable, ensure that the water detector is close
to the Converged Cabinet to facilitate further cable connections.
Step 7 Place the water detection cable onto the fastener, secure the fastener, and keep
the water detection cable in close contact with the
oor, as shown in Figure
4-151.