IDEC SmartRelay functions
IDEC SmartRelay Manual 187
When the type of analog outputs is set to 4-20mA:
When internal values less than zero are inputted to the
analog outpu
t, the analog output module outputs current
values less than 4mA.
When internal values more than 1000 are inputted to the
an
alog outpu
t, the analog output module outputs 20mA.
The relationship between the internal value Ax inputted to the analog output and
the analog output value:
Note
Using an Analog trigger, you can determine that the internal values
less than zero or more than 1000 are inputted to the analog output.
When the type of analog outputs is set to 4-20mA, and
internal values less than zero are inputted to the analog
output, it outputs current values less than 4mA. You may
need to prevent the analog output module from outputting
current values less than 4mA. To do this, connect the Analog
Multiplexer (B007) in front of the analog output (AQ1) and
connect the Analog trigger (B006) in front of the Analog
Multiplexer to convert the internal values less than zero to
internal values equal to or more than zero.
Analog output value
lnternal value Ax
0
-1000
1000
20mA
4mA
-250
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC FL1E-H12RCE and is the answer not in the manual?

IDEC FL1E-H12RCE Specifications

General IconGeneral
BrandIDEC
ModelFL1E-H12RCE
CategoryOther
LanguageEnglish

Related product manuals