IDEC SmartRelay functions
IDEC SmartRelay Manual 171
The thermocouples available have the following technical
data: -30 to +70°C, 0 to 10 VDC.
See also Chapter 4.3.6.
Configuration (example):
Press
View in parameter assignment mode (example):
Application Internal mapping
-30 to +70°C=0 to 10 V DC 0 to 1000
0°C 300
→ Offset = -30
Range of values:
-30 to +70°C=100
1000
→ Gain = 100/1000 = 0.1
On threshold = 15°C Threshold = 15
Off threshold = 5°C Threshold = 5
B3 1+
On =+00015
Off =+00005
Protection mode
On threshold
Off threshold
▲
B3 2
A =00.10
B =-00030
p=0
Gain
Offset
Decimals in the message text
(if used)
B3 1
On =+00015
Off =+00005
On threshold
Off threshold
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com