Technical data
258
IDEC SmartRelay Manual
A.2 Technical data: FL1C-...12RCC
and FL1B-M08C2R2
FL1C-H12RCC
FL1C-B12RCC
FL1B-M08C2R2
Power supply
Input voltage 100...240 V AC/DC 100...240 V AC/DC
Permissible range 85 ... 265 V AC
100 ... 253 V DC
85 ... 265 V AC
100 ... 253 V DC
Permissible mains frequency 47 ... 63 Hz 47 ... 63 Hz
Power consumption
100 V AC
240 V AC
100 V DC
240 V DC
10 ...40 mA
10 ... 25 mA
5 ... 25 mA
5 ... 15 mA
10 ... 30 mA
10 ... 20 mA
5 ... 15 mA
5 ... 10 mA
Voltage failure buffering
100 V AC
240 V AC
typ. 10 ms
typ. 20ms
typ. 10 ms
typ. 20ms
Power loss at
100 V AC
240 V AC
100 V DC
240 V DC
1.1 ...4.6W
2.4 ... 6 W
0.5 ... 2.9 W
1.2 ... 3.6 W
1.1 ...3.5W
2.4 ... 4.8 W
0.5 ... 1.8 W
1.2 ... 2.4 W
Backup of the real-time clock
at 25 °C
typ. 80 h 4
Accuracy of the real-time clock typ. ±2 s/day
Digital inputs
Number 8 4
Electrical isolation No No
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com