Parameter Groups
‑101‑
2: AI2
The frequency upper limit is input by current or voltage signal through the AI2.
The frequency is calculated according to the preset AI curve.
3: AI3
The frequency upper limit is input by current or voltage signal through the AI3.
The frequency is calculated according to the preset AI curve.
4: Pulse reference (DI5)
The frequency upper limit is set through the DI5. The frequency is calculated
based on the curve of the relationship between the pulse frequency and the
maximum frequency.
5: Communication
The frequency upper limit is set through communication.
6: Multi‑reference
F0-12
Frequency upper limit
Address:
0xF00C
Min.:
F0‑14
Unit:
Hz
Max.: F0‑10 Data type: UInt16
Default:
50
Change: In real time
Value Range:
F0‑14 to F0‑10
Description
This parameter defines the maximum running frequency allowed for the motor.
F0-13
Frequency upper limit offset
Address:
0xF00D
Min.:
0
Unit:
Hz
Max.: F0‑10 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.00 Hz to F0‑10
Description
This parameter defines the offset of the frequency upper limit. It is used to adjust
the output frequency upon minimum frequency reference signal when the
frequency is set by an external analog signal (voltage or current).
F0-14
Frequency lower limit
Address:
0xF00E
Min.:
0
Unit:
Hz
Max.: F0‑12 Data type: UInt16
Default:
0
Change: In real time