Parameter Groups
‑105‑
F0-25
Acceleration/Deceleration time base frequency
Address:
0xF019
Min.:
0
Unit:
‑
Max.: 2 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Maximum frequency (F0‑10)
1: Frequency reference
2: 100 Hz
Description
This parameter defines the target frequency during acceleration and the start
frequency during deceleration.
F0-26
Base frequency for UP/DOWN modification during running
Address:
0xF01A
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Running frequency
1: Frequency reference
Description
This parameter defines the base frequency from which the target frequency is
adjusted by using the UP/DOWN key of the operating panel during operation.
If it is set to 0 and the running frequency is 25 Hz, the target frequency will change
from 25 Hz at a certain rate when the UP key is pressed.
If it is set to 1, the target frequency will change from the original target frequency
when the UP key is pressed.
F0-27
Main frequency coefficient
Address:
0xF01B
Min.:
0
Unit:
%
Max.: 100 Data type: UInt16
Default:
10
Change: In real time
Value Range:
0.00% to 100.00%
Description
This parameter defines the main frequency reference coefficient when the
frequency superposition mode is Main x Auxiliary. The value 100.00% corresponds
to the target main frequency reference.