Parameter Groups
‑108‑
F1-05
Rated motor speed
Address:
0xF105
Min.:
1
Unit:
RPM
Max.: 65535 Data type: UInt16
Default:
1460
Change:
At stop
Value Range:
1 RPM to 65535 RPM
Description
This is the speed of the rotor in RPM when the motor is running in rated
conditions.
F1-06
Asynchronous/Synchronous motor stator resistance
Address:
0xF106
Min.:
0.001
Unit:
Ω
Max.: 65.535 Data type: UInt16
Default:
1.204
Change:
At stop
Value Range:
0.001 Ω to 65.535 Ω
Description
This parameter indicates the DC resistance of stator winding of asynchronous
motor, which can be obtained by motor auto‑tuning.
F1-07
Asynchronous motor rotor resistance
Address:
0xF107
Min.:
0.001
Unit:
Ω
Max.: 65.535 Data type: UInt16
Default:
0.908
Change:
At stop
Value Range:
0.001 Ω to 65.535 Ω
Description
This parameter defines the DC resistance of rotor winding of the asynchronous
motor, which can be obtained by static auto‑tuning or dynamic auto‑tuning of the
motor.
F1-08
Leakage inductive reactance of the asynchronous motor
Address:
0xF108
Min.:
0.01
Unit:
mH
Max.: 655.35 Data type: UInt16
Default:
5.28
Change:
At stop
Value Range:
0.01 mH to 655.35 mH