Parameter Groups
‑131‑
Description
F2-44
Rotor time constant check
Address:
0xF22C
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change: Unchangeable
Value Range:
0: Disabled
1: Enabled
Description
F2-45
Torque amplitude of rotor time constant check
Address:
0xF22D
Min.:
10
Unit:
%
Max.: 100 Data type: UInt16
Default:
30
Change: Unchangeable
Value Range:
10% to 100%
Description
F2-46
Number of times of rotor time constant check
Address:
0xF22E
Min.:
1
Unit:
‑
Max.: 6 Data type: UInt16
Default:
3
Change: Unchangeable
Value Range:
1 to 6
Description
F2-47
Inertia auto-tuning
Address:
0xF22F
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Disabled
1: Enabled