Parameter List
‑13‑
Parame
ter
Address Name Value Range Default Unit Change
Method
Page
F1‑37 0xF125 Auto‑tuning
selection
0: No auto‑tuning
1: Static auto‑tuning on partial
parameters of the
asynchronous motor (Rs, Rr,
and L0)
2: Dynamic auto‑tuning on all
parameters of the
asynchronous motor (with‑
load auto‑tuning is supported)
3: Static auto‑tuning on all
parameters of the
asynchronous motor (Rs, Rr,
L0, Lm, and IO)
4: Dynamic auto‑tuning 2 of
the asynchronous motor
(inertia auto‑tuning only in
FVC mode)
5: Dynamic auto‑tuning 3 of
the asynchronous motor
(auto‑tuning on mutual
inductance curves requires no
load, light load, or pure inertia
load; supports V/f, SVC, and
FVC modes)
11: Static auto‑tuning on
partial parameters of the
synchronous motor (excluding
back EMF)
12: No‑load dynamic auto‑
tuning on all parameters of
the synchronous motor
13: Static auto‑tuning on all
parameters of the
synchronous motor (excluding
the encoder installation angle)
14: Synchronous motor inertia
auto‑tuning (only in FVC
mode)
0 ‑ At stop "
F1‑37
"
on
page 115
F2‑00 0xF200 Low‑speed speed
loop Kp
1–200 30 ‑ In real time "
F2‑00
"
on
page 117
F2‑01 0xF201 Low‑speed speed
loop Ti
0.001s to 10.000s 0.5 s In real time "
F2‑01
"
on
page 117
F2‑02 0xF202 Switchover
frequency 1
0.00 Hz to F2‑05 5 Hz In real time "
F2‑02
"
on
page 117
F2‑03 0xF203 High‑speed speed
loop Kp
1 to 200 20 ‑ In real time "
F2‑03
"
on
page 118