Parameter Groups
‑183‑
F4-37
DI3 delay
Address:
0xF425
Min.:
0
Unit:
s
Max.: 3600 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0s to 3600.0s
Description
This parameter defines the delay of the DI state change. The delay setting
function is available only for DI1, DI2, and DI3 currently.
F4-38
DI valid mode selection 1
Address:
0xF426
Min.:
0
Unit:
Max.: 11111 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
Ones: DI1 valid mode selection
0: Active high
1: Active low
Tens: DI2 valid mode selection
0: Active high
1: Active low
Hundreds: DI3 valid mode selection
0: Active high
1: Active low
Thousands: DI4 valid mode selection
0: Active high
1: Active low
Ten thousands: DI5 valid mode selection
0: Active high
1: Active low
Description
The active mode for terminals DI1 to DI5 are set by ones, tens, hundreds,
thousands, and ten thousands of this parameter.
0: Active high
The DI terminals (DI1 to DI5) are active when connected to COM and inactive
when disconnected from COM.
1: Active low
The DI terminals (DI1 to DI5) are inactive when connected to COM and active
when disconnected from COM.