Parameter Groups
‑205‑
On the AO curve, if b indicates zero offset, k indicates gain, and X indicates
standard output, the actual output Y is kX plus b (Y = kX + b). The zero offset
coefficient 100% of AO1 and AO2 corresponds to 10 V (or 20 mA). The standard
output refers to the value corresponding to the analog output of 0 to 10 V (or 0 to
20 mA) with no zero offset or gain adjustment.
Zero offset = Zero offset coefficient x 10 V (20 mA)
The AC drive supports two AOs, namely, AO1 and AO2. AO1 and AO2 can be used
to indicate the internal running parameters in the analog mode. The indicated
parameters are defined by F5‑07 and F5‑09.
F5-13
AO2 gain
Address:
0xF50D
Min.:
‑10
Unit:
‑
Max.: 10 Data type: Int16
Default:
1
Change: In real time
Value Range:
–10.00 to +10.00
Description
On the AO curve, if b indicates zero offset, k indicates gain, and X indicates
standard output, the actual output Y is kX plus b (Y = kX + b). The zero offset
coefficient 100% of AO1 and AO2 corresponds to 10 V (or 20 mA). The standard
output refers to the value corresponding to the analog output of 0 to 10 V (or 0 to
20 mA) with no zero offset or gain adjustment.
Zero offset = Zero offset coefficient x 10 V (20 mA)
The AC drive supports two AOs, namely, AO1 and AO2. AO1 and AO2 can be used
to indicate the internal running parameters in the analog mode. The indicated
parameters are defined by F5‑07 and F5‑10.
F5-17
Expansion card relay output delay
Address:
0xF511
Min.:
0
Unit:
s
Max.: 3600 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0s to 3600.0s
Description
This parameter indicates the output delay of relay on the expansion card. F5‑01
outputs an active signal after the set delay.
F5-18
Control board relay 1 output delay
Address:
0xF512