Parameter Groups
‑226‑
Description
The AC drive provides four groups of deceleration time, which can be switched by
using the DI. This parameter defines the fourth group of deceleration time.
F8-09
Jump frequency 1
Address:
0xF809
Min.:
0
Unit:
Hz
Max.: F0‑10 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.00 Hz to value of F0‑10
Description
The jump frequency enables the AC drive to avoid any frequency at which a
mechanical resonance may occur. This parameter defines the first jump
frequency. If it is set to 0, the first jump frequency is canceled.
F8-10
Jump frequency 2
Address:
0xF80A
Min.:
0
Unit:
Hz
Max.: F0‑10 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.00 Hz to value of F0‑10
Description
The jump frequency enables the AC drive to avoid any frequency at which a
mechanical resonance may occur. This parameter defines the second jump
frequency. If it is set to 0, the second jump frequency function is disabled.
F8-11
Jump frequency amplitude
Address:
0xF80B
Min.:
0
Unit:
Hz
Max.: 5 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.00 Hz to 5.00 Hz
Description