Parameter Groups
‑253‑
Max.: 6553.5 Data type: UInt16
Default:
0
Change: Unchangeable
Value Range:
0.0–6553.5
Description
This parameter shows the operation time of the AC drive upon the first fault.
F9-45
IGBT temperature upon the 1st fault
Address:
0xF92D
Min.:
‑20
Unit: °C
Max.: 120 Data type: Int16
Default:
0
Change: Unchangeable
Value Range:
‑20℃ to +120℃
Description
This parameter shows the IGBT temperature of the AC drive upon the first fault.
F9-46
Fault subcode upon the 1st fault
Address:
0xF92E
Min.:
0
Unit:
‑
Max.: 65535 Data type: UInt16
Default:
0
Change: Unchangeable
Value Range:
0 to 65535
Description
F9-47
Fault protection action selection 0
Address:
0xF92F
Min.:
0
Unit:
‑
Max.: 22022 Data type: UInt16
Default:
0
Change:
At stop
Value Range: