Parameter Groups
260
1: Decelerate to stop
The AC drive decelerates to stop.
2: Restart upon fault
The AC drive will restart upon faults.
3: Electromagnetic shorting
The AC drive enters the electromagnetic shorting state.
4: Warning
The AC drive continues to run.
5: Disabled
Fault detection is disabled.
F9-53
Fault protection action selection 6
Address:
0xF935
Min.:
0
Unit:
Max.: 55555 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
Ones (position): Value of E45
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Tens (position): Value of E60
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Hundreds (position): Value of E61
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Thousands (position): Value of E62
0: Coast to stop
5: Canceled
Ten thousands (position): Reserved
5: Canceled
Description
The fault protection actions are set by the ones, tens, hundreds, thousands, and
ten thousands places of this parameter.
0: Coast to stop
The AC drive coasts to stop.