Parameter Groups
‑259‑
4: Warning
The AC drive continues to run.
5: Disabled
Fault detection is disabled.
F9-52
Fault protection action selection 5
Address:
0xF934
Min.:
0
Unit:
‑
Max.: 55525 Data type: UInt16
Default:
101
Change:
At stop
Value Range:
Ones (position): Value of E31
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Tens (position): Value of E40
0: Coast to stop
2: Restart upon fault
Hundreds (position): Value of E41
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Thousands (position): Value of E42
0: Coast to stop
1: Decelerate to stop
2: Restart upon fault
3: Electromagnetic shorting
4: Warning
5: Canceled
Ten thousands (position): Value of E43
0: Coast to stop
1: Decelerate to stop
3: Electromagnetic shorting
4: Warning
5: Canceled
Description
The fault protection actions are set by the ones, tens, hundreds, thousands, and
ten thousands places of this parameter.
0: Coast to stop
The AC drive coasts to stop.