Parameter Groups
‑258‑
Min.:
0
Unit:
‑
Max.: 55555 Data type: UInt16
Default:
51111
Change:
At stop
Value Range:
Ones (position): Value of E26
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Tens position: Value of E27
0: Coast to stop
1: Decelerate to stop
3: Electromagnetic shorting
4: Warning
5: Canceled
Hundreds (position): Value of E28
0: Coast to stop
1: Decelerate to stop
3: Electromagnetic shorting
4: Warning
5: Canceled
Thousands (position): Value of E29
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Ten thousands (position): Value of E30
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Description
The fault protection actions are set by the ones, tens, hundreds, thousands, and
ten thousands places of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
2: Restart upon fault
The AC drive will restart upon faults.
3: Electromagnetic shorting
The AC drive enters the electromagnetic shorting state.