Parameter Groups
‑257‑
F9-50
Fault protection action selection 3
Address:
0xF932
Min.:
0
Unit:
Max.: 55550 Data type: UInt16
Default:
5040
Change:
At stop
Value Range:
Ones (position): Reserved
0: Coast to stop
Tens (position): Value of E63
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Hundreds (position): Value of E23
0: Coast to stop
5: Canceled
Thousands (position): Value of E24
0: Coast to stop
5: Canceled
Ten thousands (position): Value of E25
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Description
The fault protection actions are set by the ones, tens, hundreds, thousands, and
ten thousands places of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
2: Restart upon fault
The AC drive will restart upon faults.
3: Electromagnetic shorting
The AC drive enters the electromagnetic shorting state.
4: Warning
The AC drive continues to run.
5: Disabled
Fault detection is disabled.
F9-51
Fault protection action selection 4
Address:
0xF933