Parameter Groups
256
F9-49
Fault protection action selection 2
Address:
0xF931
Min.:
0
Unit:
Max.: 55055 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
Ones (position): Value of E16
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Tens (position): Value of E17
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Hundreds (position): Value of E18
0: Coast to stop
Thousands (position): Value of E19
0: Coast to stop
3: Electromagnetic shorting
4: Warning
5: Canceled
Ten thousands (position): Value of E20
0: Coast to stop
3: Electromagnetic shorting
4: Warning
5: Canceled
Description
The fault protection actions are set by the ones, tens, hundreds, thousands, and
ten thousands places of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
2: Restart upon fault
The AC drive will restart upon faults.
3: Electromagnetic shorting
The AC drive enters the electromagnetic shorting state.
4: Warning
The AC drive continues to run.
5: Disabled
Fault detection is disabled.