Parameter Groups
270
0: AI1
1: AI2
2: AI3
3: AI1 AI2
4: Pulse reference (DI5)
5: Communication
6:AI1 + AI2
7: Max. (|AI1|, |AI2|)
8: Min. (|AI1|, |AI2|)
Description
This parameter defines the PID feedback source.
FA-03
PID action direction
Address:
0xFA03
Min.:
0
Unit:
Max.: 1 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Forward
1: Reverse
Description
0: Forward
When the feedback value is lower than the PID reference, the output frequency of
the AC drive increases.
1: Reverse
When the feedback value is lower than the PID reference, the output frequency of
the AC drive decreases.
FA-04
PID reference and feedback range
Address:
0xFA04
Min.:
0
Unit:
Max.: 65535 Data type: UInt16
Default:
1000
Change: In real time
Value Range:
0 to 65535
Description
This parameter is used for display of the PID reference and feedback, which are
dimensionless. For example, if this parameter is set to 1000, the PID reference (0%
to 100%) corresponds linearly to the feedback value (0 to 1000).
FA-05
Proportional gain Kp1
Address:
0xFA05