Parameter Groups
‑276‑
Value Range:
0.0% to FA‑20
Description
The value 100% corresponds to the maximum deviation between the reference
and feedback. The setting range is 0.0% to FA‑20 (PID parameter switchover
deviation 2).
FA-20
PID parameter switchover deviation 2
Address:
0xFA14
Min.:
FA‑19
Unit:
%
Max.: 100 Data type: UInt16
Default:
80
Change: In real time
Value Range:
FA‑19 to 100.0%
Description
The value 100% corresponds to the maximum deviation between the reference
and feedback. The setting range is FA‑19 (PID parameter switchover deviation 1)
to 100.0%.
FA-21
PID initial value
Address:
0xFA15
Min.:
0
Unit:
%
Max.: 100 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0% to 100.0%
Description
When the AC drive starts up, the PID starts closed‑loop algorithm only after the
PID output is fixed to the PID initial value (FA‑21) and lasts the time longer than
the value of FA‑22 (PID initial value active time).
FA-22
PID initial value holding time
Address:
0xFA16
Min.:
0
Unit:
s
Max.: 650 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.00s to 650.00s
Description
When the AC drive starts up, the PID starts closed‑loop algorithm only after the
PID output is fixed to the PID initial value (FA‑21) and lasts the time longer than
the value of FA‑22 (PID initial value active time).