Parameter Groups
‑277‑
FA-23
Maximum deviation between two PID outputs in forward direction
Address:
0xFA17
Min.:
0
Unit:
%
Max.: 100 Data type: UInt16
Default:
1
Change: In real time
Value Range:
0.00% to 100.00%
Description
FA-24
Maximum deviation between two PID outputs in reverse direction
Address:
0xFA18
Min.:
0
Unit:
%
Max.: 100 Data type: UInt16
Default:
1
Change: In real time
Value Range:
0.00% to 100.00%
Description
FA-25
PID integral property
Address:
0xFA19
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Disabled
1: Enabled
Description
0: Disabled. When the integral pause is disabled, it remains inactive no matter
whether the multi‑functional DI is active.
1: Enabled. When the integral pause is enabled and the DI allocated with the PID
integral pause function is active (F4‑00 = 22), the PID integral operation stops. In
this case, only proportional and differential operations take effect.
FA-26
Detection level of PID feedback loss
Address:
0xFA1A
Min.:
0
Unit:
%
Max.: 100 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0% to 100.0%