Parameter Groups
‑279‑
Max.: 100 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0% to 100.0%
Description
When FB‑01 is set to 0, the wobble amplitude is 0 and the wobble function does
not work. When the wobble is related to the central frequency (FB‑00 = 0), the
wobble is calculated based on the following formula: wobble = F0‑07 x FB‑01.
When the wobble is related to the maximum frequency (FB‑00 = 1), the wobble is
calculated based on the following formula: wobble = F0‑10 x FB‑01.
FB-02
Jump frequency amplitude
Address:
0xFB02
Min.:
0
Unit:
%
Max.: 50 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0% to 50.0%
Description
This parameter and the wobble are used to define the jump frequency, namely,
jump frequency = wobble x FB‑02. The wobble running frequency is limited by the
frequency upper limit and frequency lower limit.
FB-03
Wobble cycle
Address:
0xFB03
Min.:
0.1
Unit:
s
Max.: 3,000 Data type: UInt16
Default:
10
Change: In real time
Value Range:
0.1s to 3000.0s
Description
This parameter defines the time of a complete wobble cycle.
FB-04
Triangular wave rising time coefficient
Address:
0xFB04
Min.:
0.1
Unit:
%
Max.: 100 Data type: UInt16
Default:
50
Change: In real time
Value Range:
0.1% to 100.0%