Parameter Groups
‑288‑
‑100.0% to +100.0%
Description
Same as FC‑00
FC-15
Multi-reference 15
Address:
0xFC0F
Min.:
‑100
Unit:
%
Max.: 100 Data type: Int16
Default:
0
Change: In real time
Value Range:
‑100.0% to +100.0%
Description
Same as FC‑00
FC-16
Simple PLC running mode
Address:
0xFC10
Min.:
0
Unit:
‑
Max.: 2 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Stop after running for one cycle
1: Keep final values after running for one cycle
2: Repeat after running for one cycle
Description
When the simple PLC is used as the main frequency source, the running mode of
the simple PLC is set by FC‑16. FC‑17 is used to determine whether the running
stage and running frequency of the PLC before power failure are memorized upon
power failure or shutdown.
0: Stop after running for one cycle
The AC drive stops automatically after running for one cycle and starts again only
after receiving a running command.
1: Keep the final value after running for one cycle
The AC drive keeps the final running frequency and direction after running for one
cycle and starts to run from the initial PLC state upon restart.
2: Repeat after running for one cycle
The AC drive automatically starts another cycle after running for one cycle and
stops only after receiving a stop command.
FC-17
Simple PLC retention selection upon power failure
Address:
0xFC11
Min.:
0
Unit:
‑