Parameter Groups
‑289‑
Max.: 11 Data type: UInt16
Default:
0
Change: In real time
Value Range:
Ones (position): Retention selection upon power failure
0: No
1: Yes
Tens (position): Retention selection upon stop
0: No
1: Yes
Description
When the simple PLC is used as the main frequency, the running mode of the
simple PLC is set by FC‑16.
FC‑17 is used to determine whether the running stage and running frequency of
the PLC before power failure are memorized upon power failure or shutdown.
Ones (position): Retention selection upon power failure
This parameter defines whether the PLC process starts all over again upon power‑
on. When it is set to 1, the AC drive retains the PLC running stage and running
frequency before power failure and continues to run from the retained values
after the drive is powered on again.
Tens: Retention selection upon stop
This parameter defines whether the PLC process starts all over again upon
startup. When it is set to 1, the AC drive retains the PLC running stage and running
frequency before stop and continues to run from the retained values after the
drive is started again.
FC-18
Running time of speed reference 0 set by simple PLC
Address:
0xFC12
Min.:
0
Unit:
s (h)
Max.: 6553.5 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0s (h) to 6553.5s (h)
Description
FC‑18 to FC‑49 respectively define the running time and acceleration and
deceleration time of each of the 16 multi‑speed references. The running time of
each reference is the sum of acceleration or deceleration time and running time
at constant speed and target frequency.