Parameter Groups
366
30 to 150
Description
A9-05
Speed filter time of asynchronous motor in SVC mode
Address:
0xA905
Min.:
5
Unit:
ms
Max.: 32 Data type: UInt16
Default:
15
Change: In real time
Value Range:
5 ms to 32 ms
Description
A9-06
Speed feedback handling in speed control of asynchronous motor in SVC
mode
Address:
0xA906
Min.:
0
Unit:
Max.: 4 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: No operation
1: Minimum synchronization frequency limited based on load change
2: Fixed current output during low‑speed running
3: Fixed current output during low‑speed running and light load
4: Low torque optimization
Description
A9-07
Magnetic field regulation bandwidth of asynchronous motor in SVC mode
Address:
0xA907
Min.:
0
Unit:
Max.: 8 Data type: UInt16
Default:
2
Change: In real time
Value Range:
0.08.0
Description
A9-08
Low-speed running current of asynchronous motor in SVC mode
Address:
0xA908