Parameter Groups
‑391‑
Description
When PT1000 analog voltage correction is carried out on AI3, a correction curve is
formed through two points. Each point corresponds to a measured voltage and a
displayed voltage. The measured voltage is the voltage measured using a meter,
and the displayed voltage is the PTC voltage before correction (U0‑47).
AC-27
PT1000 displayed voltage 2
Address:
0xAC1B
Min.:
0
Unit:
V
Max.: 3.3 Data type: Int16
Default:
2.16
Change: In real time
Value Range:
0.000 V to 3.3 V
Description
When PT1000 analog voltage correction is carried out on AI3, a correction curve is
formed through two points. Each point corresponds to a measured voltage and a
displayed voltage. The measured voltage is the voltage measured using a meter,
and the displayed voltage is the PTC voltage before correction (U0‑47).
AC-28
AO1 measured current 1
Address:
0xAC1C
Min.:
0
Unit:
mA
Max.: 20 Data type: UInt16
Default:
4
Change: In real time
Value Range:
0.000 mA to 20.000 mA
Description
When analog current correction is carried out on the AO1, a correction curve is
formed through two points. Each point corresponds to a target voltage and a
measured current. The target current is the expected output current, and the
measured voltage is the output current actually measured.
AC-29 AO1 target current 1
Address:
0xAC1D
Min.:
0
Unit:
mA
Max.: 20 Data type: UInt16
Default:
4
Change: In real time
Value Range:
0.000 mA to 20.000 mA