B1-05
Frequency acceleration time in torque control mode
Address:
0xB105
Min.:
0
Unit:
s
Max.: 6500 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0s to 6500.0s
Description
Set B1‑05 and B1‑06 to change the slope of the frequency upper limit with time.
In tension mode, the frequency upper limit affects the motor output. Generally, it
does not need to be set. In special cases, B1‑05 and B1‑06 can be set according to
output requirements.
B1-06
Frequency deceleration time in torque control mode
Address:
0xB106
Min.:
0
Unit:
s
Max.: 6500 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0s to 6500.0s
Description
Set B1‑05 and B1‑06 to change the slope of the frequency upper limit with time.
In tension mode, the frequency upper limit affects the motor output. Generally, it
does not need to be set. In special cases, B1‑05 and B1‑06 can be set according to
output requirements.
B1-07
Friction force compensation
Address:
0xB107
Min.:
0
Unit:
%
Max.: 50 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0% to 50.0%
Description
In tension control mode, the AC drive automatically sets the target torque
according to the tension reference and roll diameter. The target torque is
increased (winding)/decreased (unwinding) according to B1‑07 to offset the effect
of friction on material tension. This parameter corresponds to the percentage of
rated torque of the AC drive.
B1-08
Mechanical inertia compensation coefficient
Address:
0xB108