Function Application
‑557‑
Step
Parameter Setting
1
Set the VDI1 function to "emergency stop" (set A1‑00 to 47).
2
Set the VDI1 active state source to parameters (set A1‑05 to
00000).
3
Modify the ones position of A1‑06 through communication.
After the preceding steps, emergency stop can be implemented by setting the
ones position of A1‑06 to 1.
Parameters
Para.
Function
Default Value Range
Description
A1‑00
VDI1 function
0 0–93 Same as F4‑00
A1‑01
VDI2 function
0
A1‑02
VDI3 function
0
A1‑03
VDI4 function
0
A1‑04
VDI5 function
0
A1‑05 VDI state source 00000 Ones:
0: Parameter
setting (A1‑06)
1: DO state
2: DI state
Tens:
0: Parameter
setting (A1‑06)
1: DO state
2: DI state
The VDIx (x ranges from 1 to
5) state is set through the
ones to ten thousands
positions of this parameter.
0: Decided by the state of
VDOx.
The state of VDI depends on
the state of VDO. VDI1 is
bound to VDO1, VDI2 is
bound to VDO2, and VDOx is
bound to VDOx (x ranges
from 1 to 5).
1: Decided by A1‑06.
The state of VDIx (x ranges
from 1 to 5) is set through
the binary bits of A1‑06.