Function Application
‑558‑
Para.
Function
Default Value Range
Description
Continued Continued
Contin
ued
Hundreds:
0: Parameter
setting (A1‑06)
1: DO state
2: DI state
Thousands
0: Parameter
setting (A1‑06)
1: DO state
2: DI state
Ten thousands
0: Parameter
setting (A1‑06)
1: DO state
2: DI state
Continued
A1‑06 VDI state 00000 Ones:
0: Disabled
1: Enabled
Tens:
0: Disabled
1: Enabled
Hundreds:
0: Disabled
1: Enabled
Thousands
0: Disabled
1: Enabled
Ten thousands
0: Disabled
1: Enabled
The VDIx (x ranges from 1 to
5) state is set through the
ones to ten thousands
positions of this parameter.
3.3.4 AI
The AC drive is equipped with three multi‑functional analog input (AI) terminals by
default. To use AIs as DIs, the following parameters need to be set. When AI input
voltage is higher than 7 V, AI is in high level state. When AI input voltage is lower than
3 V, AI is in low level state. AI is in hysteresis state when AI input voltage is between 3
V and 7 V. The following figure shows the relationship between AI input voltage and DI
state.