Function Application
676
corresponding to every bit according to binary F7‑05 (Stop state display
parameter).
For example, to view a running state parameter (such as running frequency, bus
voltage, output voltage, output current, output power, and PID reference) on the
panel, do the following:
Set the byte of F7‑03 (LED display of parameters during operation 1) corresponding
to that parameter to 1. Convert the binary number to the hexadecimal equivalent,
and set F7‑03 to the hexadecimal number. For details about the conversion
method, see "
Table 3–45 Binary‑to‑hexadecimal conversion
"
on page 679
. Press the
key on the operating panel to switch between bytes of F7‑03 to view parameter
settings.
You can view other monitoring parameters in the same way. Relationship between
monitoring parameters and bytes of F7‑03, F7‑04, and F7‑05 is summarized in the
following table.