Function Application
‑677‑
Table 3–44 Relationship between monitoring parameters and bytes of F7‑03, F7‑04, and F7‑
05
Parame
ter
Function
Default Value Range
Description
F7‑03 LED
running
display
parameter
1
0x1F
0000 to the
value of
0xFFFF
If a parameter needs to be displayed
during running, set its corresponding
bit to 1. After converting this binary
number to a hexadecimal number, set
F7‑03 to this hexadecimal number.
Note: Shaded parameters are
displayed by default.
F7‑04 LED
running
display
parameter
2
0 0000 to
value of
0xFFFF
If a parameter needs to be displayed
during running, set its corresponding
bit to 1. After converting this binary
number to a hexadecimal number, set
F7‑04 to this hexadecimal number.