Parameter Groups
98
F0-06
Range of auxiliary frequency reference Y upon superposition
Address:
0xF006
Min.:
0
Unit:
%
Max.: 150 Data type: UInt16
Default:
100
Change: In real time
Value Range:
0% to 150%
Description
F0-07
Frequency source superposition selection
Address:
0xF007
Min.:
0
Unit:
Max.: 44 Data type: UInt16
Default:
0
Change: In real time
Value Range:
Ones (position): Frequency reference selection
0: Main frequency reference X
1: Main and auxiliary operation result (based on tens position)
2: Switchover between the main frequency X and the auxiliary frequency Y
3: Switchover between the main frequency X and the main and auxiliary operation
result
4: Switchover between the auxiliary frequency Y and the main and auxiliary
operation result
Tens (position): Main and auxiliary operation of the frequency reference
0: Main + Auxiliary
1: Main Auxiliary
2: Max. (main, auxiliary)
3: Min. (main, auxiliary)
4: Main x Auxiliary
Description
Ones position: Frequency reference selection
0: Main frequency reference X
The running frequency of the AC drive is directly determined by the main
frequency reference X.
1: Main and auxiliary operation result (based on the tens place)
The running frequency of the AC drive is the calculation result of the main and
auxiliary frequencies, and the calculation method is determined by the tens
position of the value of F0‑07.