Parameter Groups
‑99‑
2: Switchover between the main frequency reference X and auxiliary frequency
reference Y
The running frequency of the AC drive is selected or switched between the main
frequency reference X and the auxiliary frequency reference Y through the DI. In
this case, the function of the DI must be set to the frequency source switching
function. For example, if the DI2 is used for switchover, set F4‑01 to 18.
3: Switchover between the main frequency reference X and the main and auxiliary
operation result
The running frequency of the AC drive is selected or switched between the main
frequency reference X and the main and auxiliary operation result through the DI.
4: Switchover between the auxiliary frequency reference Y and the main and
auxiliary operation result
The running frequency of the AC drive is selected or switched between the
auxiliary frequency reference Y and the main and auxiliary operation result
through the DI.
Tens (position): Frequency reference main and auxiliary operation
0: Main + Auxiliary
The main and auxiliary operation result is the main frequency X plus the auxiliary
frequency Y.
1: Main – Auxiliary
The main and auxiliary operation result is the main frequency X minus the
auxiliary frequency Y.
2: Maximum value
The main and auxiliary operation result is the larger value between the main
frequency X and the auxiliary frequency Y.
3: Minimum value
The main and auxiliary operation result is the smaller value between the main
frequency X and the auxiliary frequency Y.
4: Main x Auxiliary
The main and auxiliary operation result is the main frequency X multiplied by the
auxiliary frequency Y.
F0-08
Preset frequency
Address:
0xF008
Min.:
0
Unit:
Hz
Max.: F0‑10 Data type: UInt16
Default:
50
Change: In real time
Value Range:
0.00 Hz to F0‑10
Description
This parameter defines the target frequency.