Goodrive300-01A-RT series integrated machine Function description
-48-
Function
code
Name
Description
Default
Modify
P07.13
Software version of
control board
1.00655.35
P07.14
Accumulated running
time
065535h
P07.15
High bit of power
consumption of the
VFD
065535 kWh (*1000)
P07.16
Low bit of power
consumption of the
VFD
0.0999.9 kWh
P07.17
VFD model
0: G type
1: P type
P07.18
Rated VFD power
0.43000.0kW
P07.19
Rated VFD voltage
501200V
P07.20
Rated VFD current
0.16000.0A
P07.21
Factory barcode 1
0x00000xFFFF
P07.22
Factory barcode 2
0x00000xFFFF
P07.23
Factory barcode 3
0x00000xFFFF
P07.24
Factory barcode 4
0x00000xFFFF
P07.25
Factory barcode 5
0x00000xFFFF
P07.26
Factory barcode 6
0x00000xFFFF
P07.27
Present fault type
0: No fault
13: Reserved
4: Overcurrent at acceleration (OC1)
5: Overcurrent at deceleration (OC2)
6: Overcurrent at constant speed (OC3)
7: Overvoltage at acceleration (OV1)
8: Overvoltage at deceleration (OV2)
9: Overvoltage at constant speed (OV3)
10: Bus undervoltage fault (UV)
11: Motor overload (OL1)
12: VFD overload (OL2)
13: Phase loss on input side (SPI)
14: Phase loss on output side (SPO)
15: Rectifier module overheating (OH1)
16: Inverter module overheating (OH2)
17: External fault (EF)
18: RS485 communication fault (CE)
P07.28
Last fault type
P07.29
2nd-last fault type
P07.30
3rd-last fault type
P07.31
4th-last fault type
P07.32
5th-last fault type

Table of Contents