SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
8
12/10/2008
ENG ASCII GPIC York Talk ISN LINC York Talk N2 ENG
PAGE PAGE Object Point Descriptive Character Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Text Position POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P43 P41 D. Monitor 115 BD 12 Sys 2 Economizer Solenoid Valve Status SSSS P43
P44 P42 D. Monitor 116 BD 13 P44
P45 P43 D. Monitor 117 BD 14 P45
P46 P44 D. Monitor 118 BD 15 P46
P47 P45 D. Monitor 119 BD 16 P47
P48 P46 D. Monitor 120 BD 17 P48
P49 P47 D. Monitor 121 BD 18 P49
P50 P48 D. Monitor 122 BD 19 S1-1 Cooling Type: 0=Water, 1=Glycol S S S S P50
P51 P49 D. Monitor 123 BD 20 Local/Remote Control Mode: 0 = Local, 1 = Remote SSSS P51
P52 P50 D. Monitor 124 BD 21 Display Units Mode: 0 = Imperial, 1 = SI SSSS P52
P53 P51 D. Monitor 125 BD 22 P53
P54 P52 D. Monitor 126 BD 23 P54
P55 P53 D. Monitor 127 BD 24 P55
P56 P54 Code Monitor 128 ADI 1 *Sys 1 Operational Code SSSS P56
P57 P55 Code Monitor 129 ADI 2 *Sys 1 Fault Code SSSS P57
P58 P56 Code Monitor 130 ADI 3 *Sys 2 Operational Code SSSS P58
P59 P57 Code Monitor 131 ADI 4 *Sys 2 Fault Code SSSS P59
P60 P58 Code Monitor 132 ADI 5 Sys 1 Flash Tank Level (%) SSSS P60
P61 P59 Code Monitor 133 ADI 6 Sys 1 Condenser Fan Stages Running (0-6) SSSS P61
P62 P60 Code Monitor 134 ADI 7 Sys 2 Flash Tank Level (%) SSSS P62
P63 P61 Code Monitor 135 ADI 8 Sys 2 Condenser Fan Stages Running (0-6) SSSS P63
P64 P62 Code Monitor 136 ADI 9 Lead System Number SSSS P64
P65 P63 Code Monitor 137 ADI 10 Sys 1 & 2 Debug Code SSSS P65
P66 P64 A. Monitor 138 - 141 ADF 30 Local Leaving Chilled Liquid Setpoint S S S S P66
P67 P65 A. Monitor 142 - 145 ADF 31 Low Leaving Chilled Liquid Temp Cutout S S S S P67
P68 P66 A. Monitor 146 - 149 ADF 32 Sys 1 Flash Tank Drain Valve % Open SSSS P68
P69 P67 A. Monitor 150 - 153 ADF 33 Sys 2 Flash Tank Drain Valve % Open SSSS P69
P70 P68 A. Monitor 154 - 157 ADF 34 Low Suction Pressure Cutout SSSS P70
P71 P69 A. Monitor 158 - 161 ADF 35 VSD DC Bus Voltage SSSS P71
P72 P70 A. Monitor 162 - 165 ADF 36 Remote Leaving Chilled Liquid Setpoint S S S S P72
P73 P71 A. Monitor 166 - 169 ADF 37 Sys 1 Suction Superheat SSSS P73
P74 P72 A. Monitor 170 - 173 ADF 38 Cooling Range SSSS P74
P75 P73 A. Monitor 174 - 177 ADF 39 Sys 1 Discharge Superheat SSSS P75
P76 P74 A. Monitor 178 - 181 ADF 40 Sys 2 Suction Temperature SSSS P76
P77 P75 A. Monitor 182 - 185 ADF 41 Sys 2 Discharge Temperature SSSS P77
P78 P76 A. Monitor 186 - 189 ADF 42 Sys 2 Suction Superheat SSSS P78
P79 P77 A. Monitor 190 - 193 ADF 43 Sys 2 Discharge Superheat SSSS P79
P80 P78 D. Monitor 194 BD 25 Sys 1 Lockout N N S S P80
P81 P79 D. Monitor 195 BD 26 Sys 2 Lockout N N S S P81
P82 P80 D. Monitor 196 BD 27 P82
P83 P81 D. Monitor 197 BD 28 P83
P84 P82 D. Monitor 198 BD 29 P84
NOTE: The Appropriate Product Code Listing Summary Should Accompany Document
Revision: YCAV_YCIV Latitude (Rev J_04).xls Tab: YCAV_YCIV (1 & 2 Comps) Property of Johnson Controls, York, PA Page: 2
TABLE 29 - YORKTALK 2 COMMUNICATIONS DATA MAP (CONT’D)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls York YCIV A Series and is the answer not in the manual?

Johnson Controls York YCIV A Series Specifications

General IconGeneral
BrandJohnson Controls
ModelYork YCIV A Series
CategoryChiller
LanguageEnglish

Related product manuals