Kinco FD5 AC series servo driver user manual Chapter 3 Servo system interface and wiring
29
Note
After the drive or motor IIT fault (fault code: 008.0) occurs, stop the drive and check the cause of
the fault before running. If the fault fails to be checked and the drive IIT fault occurs again, it
needs to stand for more than ten minutes, and then power on the drive after cooling. Otherwise,
frequent overload failures may cause damage to the drive hardware!
Figure 3-11 200W motor overload characteristic curve
Figure 3-12 400W motor overload characteristic curve
Panel
Name
CANopen
Modbus
Type
Data type
Detailed explanation
D1.02
Motor IIT actual utilization
2FF01010
2A00
RL
Unsigned8
The actual load rate of the motor
D1.04
Actual drive IIT utilization
2FF01110
2A01
RL
Unsigned8
The actual load rate of the drive
200W motor overload characteristic curve
Overload running
time
Overload ratio
400W motor overload characteristic curve
Overload running
time
Overload ratio