EasyManua.ls Logo

Knick Stratos Multi E401N - Control Inputs

Knick Stratos Multi E401N
222 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Stratos Multi E401N
62
Pulse Frequency Controller
The pulse frequency controller is used to control a frequency-controlled actuator (metering pump).
It varies the frequency with which the contacts are switched on. The maximum pulse frequency [Imp/
min] can be configured, and is dependent on the actuator. The ON time is constant. It is automatically
calculated from the configured maximum pulse frequency.
1_
0_
1_
0_
1
2
3
1 ON time 3 Pulse frequency (Y = 80%)
2 Pulse frequency (Y = 20%)
Adjustable Controlled Variables
Sensor type Controlled variable
pH, ORP pH value, ORP, temperature
Conductivity Conductivity, temperature,
with TAN option FW-E009: Concentration (liquid)
Oxygen Saturation %air, saturation %O
2
, temperature
See also
Basics of PID Control, p. 215
5.5.4 Control Inputs
Stratos Multi provides 2 digital optocoupler inputs (OK1, OK2).
The following functions (depending on the parameter setting) can be started via the control signals:
Input OK1: off, parameter set selection, flow, function check total, or function check channel
The function of optocoupler input OK1 is defined in the System Control :
Parameter Setting
System Control
Function Control Function Control, p. 46
Input OK2: off, function check total, or functional check channel.
Selection in the menu Parameter Setting
Inputs and Outputs
Control Inputs
Input OK2
The switching level for the control signal must be specified:
Parameter Setting
Inputs and Outputs
Control Inputs Contacts
Input OK…
Input level: Active 10 ... 30 V or active < 2 V

Table of Contents