8: Device Ports
SLC™ 8000 Advanced Console Manager User Guide 140
To reset a device port, terminating and restarting all relevant connections:
set deviceport port <Device Port # or List or Name> reset
To configure up to 4 managed power supplies for device connected to a device port:
set deviceport port <Device Port # or Name> managepower
To view the settings for one or more device ports:
show deviceport port <Device Port List or Name> [display
<ip|data|modem|logging|device>]
To view a list of all device port names:
show deviceport names
To view a list of all device port types (RJ45 or USB):
show deviceport types
To view global device port settings:
show deviceport global
To view the modes and states of one or more device port(s):
Note: You can optionally email the displayed information.
show portstatus [deviceport <Device Port List or Name>] [email <Email
Address>]
To view device port statistics and errors for one or more ports:
Note: You can optionally email the displayed information.
show portcounters [deviceport <Device Port List or Name>] [email <Email
Address>]
To zero the port counters for one or more device ports:
show portcounters zerocounters <Device Port List or Name>
Device Commands
The following CLI commands correspond to the web page entries described above.
To send commands to (or control) a device connected to an SLC unit port over the serial
port:
Note: Currently the only devices supported for this type of interaction are the Sensorsoft
devices.
set command <Device Port # or Name or List> <one or more parameters>