8400 HighLine | Parameter setting & configuration
Motor control (MCTRL)
V/f characteristic control (VFCplus)
118 L Firmware 05.00 - DMS 4.2 EN - 02/2010
Note!
4-pole asynchronous motors which are designed for a rated frequency of f = 50
Hz in star connection can be operated in delta connection when being constantly
excited up to f = 87 Hz.
Advantages:
Higher speed-setting range
73% higher power output in case of standard motors
Motor current and motor power increase by the factor .
The field weakening range starts above 87 Hz.
Generally, this process can also be used with motors which have different
numbers of pole pairs. In case of 2-pole asynchronous motors, the mechanical
limit speed must be maintained.
3
efesotomasyon.com - Lenze