Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 585
8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list
12.2 Parameter list
This chapter lists all parameters of the operating system in numerically ascending order.
C00002
Note!
The parameter descriptions are based on the software version V05.00.00.
Parameter | Name:
C00002 | Controller commands
Data type: UNSIGNED_8
Index: 24573
d
= 5FFD
h
Note:
Before switching off the supply voltage after carrying out a device command, check whether the device command
has been carried out successfully via the status display under C00003
!
Drive control (DCTRL)
: Device commands
Selection list
0Off / ready
1On / start
4 Action cancelled
5No access
6 No access controller inhibit
20 20% working
40 40% working
60 60% working
80 80% working
Subcodes Lenze setting Info
C00002/1 0: Off / ready Load Lenze setting
• All parameters are reset to the Lenze setting.
• Only possible when the controller is inhibited.
C00002/2 0: Off / ready Reserved
C00002/3 0: Off / ready Reserved
C00002/4 0: Off / ready Reserved
C00002/5 0: Off / ready Reserved
C00002/6 0: Off / ready Load all parameter sets
• All parameter sets are loaded from the memory
module.
• Only possible when the controller is inhibited.
C00002/7 0: Off / ready Reserved
C00002/8 0: Off / ready Reserved
C00002/9 0: Off / ready Reserved
C00002/10 0: Off / ready Reserved
C00002/11 0: Off / ready Save all parameter sets
• All parameter sets are saved in the memory module
with mains failure protection.
C00002/12 0: Off / ready Reserved
C00002/13 0: Off / ready Reserved
C00002/14 0: Off / ready Reserved