8400 HighLine | Parameter setting & configuration
Motor control (MCTRL)
Servo control (SC)
162 L Firmware 05.00 - DMS 4.2 EN - 02/2010
5.7.3.6 Optimising the behaviour in the field weakening range
The behaviour in the field weakening range is influenced by:
the field controller
the field weakening controller
the field feedforward control unit
adaptive adaptation of the P component of the field and speed controllers
An additional limitation of the I component of the controller when the voltage limit is
reached
Note!
In general, these settings are pre-optimised so that further optimisation is not
required.
Optimisation for special motors (e.g. mid-frequency motors) or for motors
whose power is not adapted can be carried out according to the algorithms
shown in the following sections.