8400 HighLine | Parameter setting & configuration
Motor control (MCTRL)
Monitoring
198 L Firmware 05.00 - DMS 4.2 EN - 02/2010
5.11.1 Device overload monitoring (Ixt)
C00064/1...3
displays the device utilisation (ixt) in [%] in different time intervals:
If the device utilisation reaches the switch-off threshold set in C00123
:
The error response set in C00604
will be carried out (Lenze setting: "Warning").
–The "OC5: Ixt overload
" error message will be entered into the logbook of the
controller.
–The bMctrlIxtOverload status output of the LS_DeviceMonitor
system block will be
set to TRUE.
A setting of C00604
= "0: No Reaction" deactivates the monitoring.
Parameter Info
C00064/1 Device utilisation (Ixt)
Maximum value of pulse utilisation (C00064/2
)
and permanent utilisation (C00064/3
).
C00064/2 Device utilisation (Ixt) 15s
Pulse utilisation over the last 15 seconds (only for loads >160 %).
C00064/3 Device utilisation (Ixt) 3 min
Permanent utilisation over the last 3 minutes.
Highlighted in grey = display parameter