8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00441
656 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
C00441
C00442
Parameter | Name:
C00441 | Decoupling: AnalogOut
Data type: UNSIGNED_16
Index: 24134
d
= 5E46
h
As of version 04.00.00
Configuration defining the events that lead to a decoupling of the analog output terminals.
Configuring exception handling of the output terminals
Setting range (min. hex value | max. hex value) Lenze setting
0x0000 0xFFFF 0x0000 (decimal: 0)
Value is bit-coded: (; =bit set)
Bit 0 SafeTorqueOff
Bit 1 ReadyToSwitchON
Bit 2 SwitchedON
Bit 3 Reserved
Bit 4 Trouble
Bit 5 Fault
Bit 6 Reserved
Bit 7 Reserved
Bit 8 Reserved
Bit 9 Fail CAN_Management
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved
; Read access ; Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00442 | AOutx: Decoupling value
Data type: INTEGER_16
Index: 24133
d
= 5E45
h
As of version 04.00.00
Definition of the value the analog output terminals are to have in the decoupled state.
Configuring exception handling of the output terminals
Setting range (min. value | unit | max. value)
0.00 % 100.00
Subcodes Lenze setting Info
C00442/1 0.00 % AOut1_U: Decoupling value
C00442/2 0.00 % AOut2_U: Decoupling value
C00442/3 0.00 % AOut1_I: Decoupling value
C00442/4 0.00 % AOut2_I: Decoupling value
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100