Parameter list | C00700
C00700
Parameter | Name:
C00700 | LA_NCtrl: analog connection list
Data type: UNSIGNED_16
Index: 23875
d
= 5D43
h
Connection parameters for "Actuating drive speed" application: 16-bit inputs
• Selection of the 16-bit output signals for connection with the 16-bit input signals
• The selection list contains all 16-bit output signals which can be assigned to the 16-bit inputs mapped by the
subcodes.
Selection list
See selection list - analog signals
Subcodes Lenze setting Info
C00700/1 20005: C_wDriveCtrl LA_NCtrl
: wCANDriveControl
(input for control word from CAN to device control)
C00700/2 20005: C_wDriveCtrl LA_NCtrl
: wMCIDriveControl
(input for control word from communication interface to
device control)
C00700/3 20012: nPar3_a LA_NCtrl
: nTorqueMotLim_a
(input for maximum torque in motor mode)
C00700/4 20013: nPar4_a LA_NCtrl
: nTorqueGenLim_a
(input for maximum torque in generator mode)
C00700/5 0: Not connected LA_NCtrl
: nPIDVpAdapt_a
(input for adapting the PID controller gain)
C00700/6 0: Not connected LA_NCtrl
: nPIDActValue_a
(input for actual PID controller value)
C00700/7 16000: AIN1_Out LA_NCtrl
: nMainSetValue_a
(input for main speed setpoint)
C00700/8 0: Not connected LA_NCtrl
: nAuxSetValue_a
(input for additional speed setpoint)
C00700/9 0: Not connected LA_NCtrl
: nGPAnalogSwitchIn1_a
(input for analog-value selector analog signal 1)
C00700/10 0: Not connected LA_NCtrl
: nGPAnalogSwitchIn2_a
(input for analog-value selector analog signal 2)
C00700/11 0: Not connected LA_NCtrl
: nGPArithmetikIn1_a
(input for arithmetic function analog signal 1)
C00700/12 0: Not connected LA_NCtrl
: nGPArithmetikIn2_a
(input for arithmetic function analog signal 2)
C00700/13 0: Not connected LA_NCtrl
: nGPMulDivIn_a
(input for analog signal for multiplication/division)
C00700/14 0: Not connected LA_NCtrl
: nGPCompareIn1_a
(input for comparison operation analog signal 1)
C00700/15 0: Not connected LA_NCtrl
: nGPCompareIn2_a
(input for comparison operation analog signal 2)
C00700/16 0: Not connected LA_NCtrl
: nVoltageAdd_a
(input for additive voltage boost)
C00700/17 0: Not connected LA_NCtrl
: nPIDInfluence_a
(input for influence signal of PID controller correcting
variable)
C00700/18 0: Not connected LA_NCtrl
: nPIDSetValue_a
(input for PID controller setpoint)
C00700/19 0: Not connected LA_NCtrl
: nPWMAngleOffset
(input for pulse width modulation phase offset)
C00700/20 0: Not connected LA_NCtrl
: nBoost_a
C00700/21 0: Not connected LA_NCtrl
: wSMCtrl
C00700/22 0: Not connected LA_NCtrl
: wReserved2
C00700/23 0: Not connected LA_NCtrl
: wReserved3
efesotomasyon.com - Lenze