8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00138
612 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
C00138
C00142
Parameter | Name:
C00138 | Internal control signals
Data type: UNSIGNED_16
Index: 24437
d
= 5F75
h
Bit-coded display of internal control signals from different sources
Display area (min. hex value | max. hex value)
0x0000 0xFFFF
Value is bit-coded:
Bit 0 Reserved
Bit 1 DisableVoltage
Bit 2 SetQuickStop
Bit 3 EnableOperation
Bit 4 InitFinishedOK
Bit 5 ModeSpecific_2
Bit 6 ModeSpecific_3
Bit 7 ResetFault
Bit 8 SetHalt
Bit 9 FirmwareUpdate
Bit 10 MotorIdent
Bit 11 SetMessage
Bit 12 SetIMP
Bit 13 SetSystemFail
Bit 14 SetFail
Bit 15 SetFailQSP
Subcodes Info
C00138/1 SYS control signals
C00138/2 MCK control signals
C00138/3 FWM control signals
; Read access Write access CINH PLC STOP ; No transfer COM MOT
Parameter | Name:
C00142 | Auto-start option
Data type: UNSIGNED_8
Index: 24433
d
= 5F71
h
Setting of the "Auto-start" function
• When inhibit is activated, the motor can only start after the device state has changed.
Setting range (min. hex value | max. hex value) Lenze setting
0x00 0xFF 0x09 (decimal: 9)
Value is bit-coded: (; =bit set)
Bit 0 ; Inhibit at power-on
Bit 1 Inhibit at trouble
Bit 2 Inhibit at fault
Bit 3 ; Inhibit at undervoltage
Bit 4 Reserved
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
; Read access ; Write access CINH PLC STOP No transfer COM MOT