8400 HighLine | Parameter setting & configuration
Diagnostics & error management
Error messages of the operating system
484 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
OC15: Cross current controller limitation [xx.0123.00097]
OC16: Torque controller limitation [xx.0123.00098]
FC1: Field controller limitation [xx.0123.00099]
OC6: I2xt overload - motor [xx.0123.00105]
LP1: Motor phase failure [xx.0123.00145]
Response (Lenze setting printed in bold) Setting: C00570/2 (; Adjustable response)
: None ; Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
Cross current controller limitation is active. • Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
• Check parameter setting of the current controller
with regard to the motor controllers (e.g. reduce Vp).
Motor control
Response (Lenze setting printed in bold) Setting: C00570/3 (; Adjustable response)
: None ; Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
Actuator limitation according to speed controller. • Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Motor control
Response (Lenze setting printed in bold) Setting: C00570/4 (; Adjustable response)
: None ; Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
The output of the field controller has reached its
maximum limit value. The drive is at the torque limit in
the field weakening range.
• Observe load requirements.
• Correct dimensioning or reduce setpoint from the
field weakening range if necessary.
Motor control
Response (Lenze setting printed in bold) Setting: C00606 (; Adjustable response)
; None ; Fault Trouble TroubleQuickstop : Warning WarningLocked Information
Cause Remedy
Thermal overload of the motor. • Observe load requirements.
• Correct dimensioning if necessary.
• In case of VFCplus operation: Check Vmin boost
(C00016
).
Set Vmin boost
Response (Lenze setting printed in bold) Setting: C00597 (; Adjustable response)
: None ; Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
Motor phase failure - power section
• This error message is displayed if a motor phase
carries less current of one half-wave than set in
C00599
.
• Check the motor connections and the corresponding
plug connector on the device and, if necessary, the
motor terminal box.
• Check the trigger threshold C00599.
efesotomasyon.com - Lenze