Commissioning
Safety instructions with regard to commissioning
Tip!
In the Lenze setting, the "U/f characteristic linear" operating mode has been set for
motor control. The parameter settings have been set in advance in such a way that,
if the drive controller and 50 Hz asynchronous machine match each other in terms
of performance, the drive controller is immediately ready for operation without
any further parameter setting work and the motor works satisfactorily.
Recommendations for the following application cases:
• If the drive controller and motor differ greatly from each other in terms of
performance
set code C00022 (I
max
limit in motor mode) to
• If a higher starting torque is required
set code C00016 (U
min
increase) in such a way that, at a field frequency of f =
3Hz (C00058), the rated motor current I
N(Motor)
flows.
• For noise optimisation
set code C00018 to "3" (switching frequency 16 kHz
sin var
).
• If a high torque without feedback is to be provided at small speeds, we
recommend the "Vector control" operating mode.
I
Max
2.0 I
N(motor)
×=